ioc-HOMS-XRT-PLC was reporting: Sum read 0 failed: status 1861

This is: 0x74518610x9811 0745ADSERR_CLIENT_SYNCTIMEOUTTimeout has occurred – the remote terminal is not responding in the specified ADS timeout. The route setting of the remote terminal may be configured incorrectly.

I think the associated records may not have gotten an alarm severity set - or, our clients (PyDM/typhos/PMPS diagnostic) were not appropriately rendering alarm severity widget outlines.

Technically an issue for https://github.com/pcdshub/twincat-ads ; will link it there as well.