HA-Inepro-PRO380-Mod

Enables reading out the MODBUS port on your Inepro PRO380-Mod via an ESPHome master.

Add the sensorcode to your alraedy set up ESPHome ESP32 + RS485 and enjoy.

Communication

Taken from the PRO380-Mod manual: The PRO380-Mod can be connected for Modbus communication. The Modbus implementation used is Modbus basic (standard). This means the following: Baud rate 9600 8 data bits Even parity 1 stop bit

image

Following data is available in the meter:

Live values

Reg. address Content Function code Register length Unit Data type Format
5000 Voltage* 03 2 V Float ABCD
5002 L1 Voltage 03 2 V Float ABCD
5004 L2 Voltage 03 2 V Float ABCD
5006 L3 Voltage 03 2 V Float ABCD
5008 Grid frequency 03 2 Hz Float ABCD
500A Current* 03 2 A Float ABCD
500C L1 Current 03 2 A Float ABCD
500E L2 Current 03 2 A Float ABCD
5010 L3 Current 03 2 A Float ABCD
5012 Total active power 03 2 kW Float ABCD
5014 L1 Active power 03 2 kW Float ABCD
5016 L2 Active power 03 2 kW Float ABCD
5018 L3 Active power 03 2 kW Float ABCD
501A Total reactive power 03 2 kvar Float ABCD
501C L1 Reactive power 03 2 kvar Float ABCD
501E L2 Reactive power 03 2 kvar Float ABCD
5020 L3 Reactive power 03 2 kvar Float ABCD
5022 Total apparent power 03 2 kVA Float ABCD
5024 L1 Apparent power 03 2 kVA Float ABCD
5026 L2 Apparent Power 03 2 kVA Float ABCD
5028 L3 Apparent Power 03 2 kVA Float ABCD
502A Power factor 03 2 - Float ABCD
502C L1 Power factor 03 2 - Float ABCD
502E L2 Power factor 03 2 - Float ABCD
5030 L3 Power factor 03 2 - Float ABCD

Values that 'add up'

Reg. address Content Function code Register length Unit Data type Format
6000 Total active energy 03 2 kWh Float ABCD
6002 T1 Total active energy 03 2 kWh Float ABCD
6004 T2 Total active energy 03 2 kWh Float ABCD
6006 L1 Total active energy 03 2 kWh Float ABCD
6008 L2 Total active energy 03 2 kWh Float ABCD
600A L3 Total active energy 03 2 kWh Float ABCD
600C Forward active energy 03 2 kWh Float ABCD
600E T1 Forward active energy 03 2 kWh Float ABCD
6010 T2 Forward active energy 03 2 kWh Float ABCD
6012 L1 Forward active energy 03 2 kWh Float ABCD
6014 L2 Forward active energy 03 2 kWh Float ABCD
6016 L3 Forward active energy 03 2 kWh Float ABCD
6018 Reverse active energy 03 2 kWh Float ABCD
601A T1 Reverse active energy 03 2 kWh Float ABCD
601C T2 Reverse Active Energy 03 2 kWh Float ABCD
601E L1 Reverse active energy 03 2 kWh Float ABCD
6020 L2 Reverse active energy 03 2 kWh Float ABCD
6022 L3 Reverse active energy 03 2 kWh Float ABCD
6024 Total reactive energy 03 2 kvarh Float ABCD
6026 T1 Total reactive energy 03 2 kvarh Float ABCD
6028 T2 Total reactive energy 03 2 kvarh Float ABCD
602A L1 Total reactive energy 03 2 kvarh Float ABCD
602C L2 Total reactive energy 03 2 kvarh Float ABCD
602E L3 Total reactive energy 03 2 kvarh Float ABCD
6030 Forward reactive energy 03 2 kvarh Float ABCD
6032 T1 Forward reactive energy 03 2 kvarh Float ABCD
6034 T2 Forward reactive energy 03 2 kvarh Float ABCD
6036 L1 Forward reactive energy 03 2 kvarh Float ABCD
6038 L2 Forward reactive energy 03 2 kvarh Float ABCD
603A L3 Forward reactive energy 03 2 kvarh Float ABCD
603C Reverse reactive energy 03 2 kvarh Float ABCD
603E T1 Reverse reactive energy 03 2 kvarh Float ABCD
6040 T2 Reverse reactive energy 03 2 kvarh Float ABCD
6042 L1 Reverse reactive energy 03 2 kvarh Float ABCD
6044 L2 Reverse reactive energy 03 2 kvarh Float ABCD
6046 L3 Reverse reactive energy 03 2 kvarh Float ABCD
6048 Tariff 03 1 - Signed -
6049 Resettable day counter 03 2 kWh Float ABCD